Boiler Maintenance Laporte, Indiana
Technician Invoice Notes: Serviced Boiler System. Drained Expansion Tank, Tested Relief Valve, Tested Fill Reducing Valve, Cleaned Burners, Cleaned Pilot Assembly And Cycled Boiler From The Thermostat To Ensure Proper Operation. System Is Operating Properly At This Time And Cycles Off At 180° With A Pressure Of Approximately 19 PSIG. Set Thermostat Back To Clients Set Point Of 58°.
Laporte, IN
11-08-2021
Boiler Maintenance Laporte, Indiana
Technician Invoice Notes: Serviced Boiler System. Cleaned Burners, Cleaned Pilot Assembly, Oiled Circulator Pump, Tested Relief Valve, Tested Reducing Valve, Inspected Heat Exchanger Sections, Inspected Vent And Cycled Boiler To Ensure Proper Operation. Boiler System Is Heating Properly At This Time And Cycles Off At 180° With A Pressure Of Approximately 19 Psi.
LaPorte, IN
12-29-2020
Boiler Maintenance Laporte, Indiana
Technician Invoice Notes: Call To Service Boiler System. Upon Arrival Found System Pressure High. Cleaned Burners, Cleaned Flame Sensor, Cleaned Spark Ignition Components, Cleaned Pilot Assembly, Tested Relief Valve, Could Not Drain Expansion Tanks Due To Lack Of Isolation, Replaced Rollout Cut Off Limit Due To It Breaking Upon Removal And Found Fill Reducing Valve Failed. Cycled Boiler To Ensure Proper Operation And Unit Is Heating At This Time. Observed Boiler Cycle Off At 160° With A Pressure Of Approximately 24 PSIG. Expansion Tanks Are Water Logged And System Operating Pressure Is Higher Than Recommended. Unit Needs A New Fill Reducing Valve And Expansion Tanks Drained. Created An Estimate For The Required Repairs And Emailed Estimate To Client For Scheduling.
LAPORTE, IN
12-18-2020
Boiler Maintenance Laporte, Indiana
Technician Invoice Notes: Serviced Bryant Gravity Boiler. Cleaned Burners, Cleaned Pilot Assemblies, Inspected Heat Exchanger, Inspected Vent Assemblies, Drained Expansion Tank, Tested Relief Valve, Tested Fill Reducing Valve And Cycled Boiler To Ensure Proper Operation. Observed Boiler Cycle Off At 160° With A Pressure Of Approximately 24 PSIG.
LaPorte, IN
10-20-2020
Boiler Maintenance Laporte, Indiana
Technician Invoice Notes: Serviced Boiler, Cleaned Burners, Cleaned Pilot Assembly, Replaced Thermocouple, Inspected Heat Exchanger Sections, Tested Relief Valve, Cycled All Main Floor Zones And All Radiation Is Heating. Boiler Is Heating Properly At This Time And Shuts Down At 190 Degrees @ 18 PSI. Client Requests A Mailed Receipt.
LaPorte, IN
10-06-2020
Boiler Maintenance Laporte, Indiana
Technician Invoice Notes: Serviced Boiler System, Cleaned Burners, Cleaned Flame Sensor, Cleaned Spark Igniter, Tested Pressure Relief Valve, Drained Expansion Tank, Tested Auto Fill Valve And Set System Pressure To Approximately 12 Psi Cold. Cycled Boiler System From All Zones To Ensure Proper Operation And The System Is Heating At This Time. Boiler Shuts Down At 185 Degrees With A Pressure Of Approximately 15 Psi.
LaPorte, IN
09-09-2020
Boiler Maintenance Laporte, Indiana
Technician Invoice Notes: Call To Service Boiler System. Cleaned Burners, Cleaned Thermocouple And Pilot Assembly, Inspected Expansion Tank, Tested Relief Valve And Reducing Valve And Cycled System To Ensure Proper Operation. Ensured All Boiler Drains Were Leak Free And Observed Unit Cycle Off At 180° With A Pressure Of Approximately 22 PSIG.
LaPorte, IN
07-20-2020
Weil McLain
CGA-5
I Drained the boiler system.
Provided and installed one new Taco 3 speed circulator.
Provided and installed one new Extrol bladder expansion tank.
Provided and installed one new temperature / pressure safety relief valve.
Removed and disposed of one existing cast iron radiator on the second floor.
Provided and installed one new 12 foot section of baseboard radiation on the outside wall.
Re-filled boiler system and bled radiation.
Tested system safeties and operation.
LAPORTE,
IN
03-18-2020