Furnace Service And Repair La Porte, Indiana
Technician Invoice Notes: Call For No Heat. Upon Arrival Cycled Furnace Several Times Finding Board Randomly Dropping Power To Furnace Components. Checked For Proper Incoming Voltage To Board Finding Constant 120v. Checked Power To And From Transformer Finding Constant Proper Voltage. Determined Control Board Is Failed. Replaced Control Board And Tested Operation. Furnace Is Heating At This Time With A Temperature Rise Of 52°. Checked Primary Heat Exchanger Cells Finding No Failures At This Time.
La Porte, IN
02-07-2024
Furnace Service And Repair La Porte, Indiana
Call For No Heat. Upon Arrival Found Furnace Code For Main Limit. After Investigation Found Main Limit Stuck Open. Tapped Limit To Get It To Close. Cycled Furnace From Thermostat And Observed Operation. Furnace Is Heating Within Allowed Range At 58°. Found Several Blocked Returns In Floor. Recommend To Customer To Remove Obstacles. Also Recommended To Customer To Replace Main Limit. Get Customer Price And Availability. Inspected Primary Heat Exchanger Cells Finding No Failures At This Time. Checked For Carbon Monoxide Finding 0ppm At This Time.
La Porte, IN
01-10-2024
Furnace Service And Repair La Porte, Indiana
Technician Invoice Notes: Call For Intermittent Heat. Upon Arrival Cycled Furnace And Observed Operation. Found Burner In Front Of Flame Sensor Lighting Shortly After First Two Burners, Causing Lockout To Occur Occasionally. Performed Furnace Service And Clean As Preventative Maintenance And To Correct Improper Ignition. Inspected Heat Exchanger Finding No Failures At This Time. Inspected Blower Wheel, Evaporator Coil And Air Filter. Cleaned Flame Sensor, Burners And Crossovers. Vaccumed Furnace Exhaust. Cleared Inducer Signal Port. Cycled Furnace And Observed Operation. Furnace Is Heating Properly At This Time With A Temperature Rise Of 50°. Tested For Carbon Monoxide Finding 0ppm At This Time. Customer Wants Paper Receipt Mailed To House.
La Porte, IN
01-28-2022
Furnace Service And Repair La Porte, Indiana
Technician Invoice Notes: Call For No Heat. Upon Arrival Found Furnace Shutting Off Shortly After Flames Came On. Furnace Was Giving Code For Low Flame Signal. Suggested And Performed Furnace Service And Clean. Inspected Heat Exchangers Finding No Failures At This Time. Inspected Blower Wheel, Evaporator Coil And Air Filter. Cleaned Flame Sensor, Inspected Burners And Crossovers. Cleared Inducer Signal Port And Drain Lines. Measured Ignitor Resistance At 86 Ohms. Cycled Furnace And Observed For Proper Operation. Furnace Is Heating Properly At This Time With A Temperature Rise Of 55°. Tested For Carbon Monoxide Finding 0ppm At This Time.
La Porte, IN
01-28-2022
Furnace Service And Repair La Porte, Indiana
Technician Invoice Notes: Replaced Cracked Collector Box And Tested Operation Of Furnace. Furnace Is Operating Properly At This Time. Returned For Furnace Short Cycling. Found Slightly Obstructed Drain Line Causing Pressure Switch To Stick Due To Water. Cleared Drain Line And Cycled Furnace To Insure Proper Operation. Furnace Is Operating Properly At This Time.
LA PORTE, IN
12-10-2021
Furnace Service And Repair La Porte, Indiana
Technician Invoice Notes: Call For No Heat. Upon Arrival Found Failed Inducer Motor. Inspected Heat Exchanger Assembly And Found No Failures At This Time. Need To Call Client With Price And Availability For A Replacement Inducer Motor Assembly As Soon As Possible.
La Porte, IN
12-02-2021
Furnace Service And Repair La Porte, Indiana
Technician Invoice Notes: Call To Replace Thermostat. Upon Arrival Found Failed White Rogers Thermostat. Provided And Installed A New Honeywell Focus Pro 5000 Non-programmable Thermostat And Tested Equipment Operation.
La Porte, IN
12-02-2021
Furnace Service And Repair La Porte, Indiana
INVOICE NOTE:
Technician Invoice Notes: Call For Water Leaking From Furnace. Found Collector Box Leaking From Seal. Removed Collector Box And Resealed With Heat Resistant Silicone. Reassembled Furnace And Observed Operation. Furnace Is Operating And Heating Properly With No Leaks At This Time. Temp Rise 51°. Inspected Heat Exchangers Finding No Failures At This Time. Primary Heat Exchanger Is Showing Signs Of Fatigue. Tested For Carbon Monoxide Finding 0ppm At This Time.
La Porte, IN
11-30-2021
Furnace Service And Repair La Porte, Indiana
Technician Invoice Notes: Upon Arrival Found Furnace Giving Code For Tripped Limit. Limit Reset Automatically And Tripped Again After Over Heating. Customer Stated Furnace Was Converted To Natural Gas From Propane. Adjusted Gas Valve Lower. Cycled Furnace To Insure Proper Operation. Furnace Is Heating Properly At This Time With A Temperature Rise Of 50°. Reschedule For 11-17-21 To Have Gas Valve Set Properly With Manometer.
Returned To Set Gas Pressure Properly. Set To 3.2” Wc. Replaced Gas Valve Spring With Natural Gas Spring (lp Spring Was Not Converted Properly). Set Blower Speed To Full Speed. Cycled Furnace To Insure Proper Operation. Furnace Is Heating Properly At This Time With A Temperature Rise Of 53°.
La Porte, IN
11-30-2021
Furnace Service And Repair La Porte, Indiana
Technician Invoice Notes: Call For No Heat. Upon Arrival Cycled Furnace And Found Burners Not Lighting Properly. Burner In Front Of Flame Sensor Was Slow To Light. Suggested And Performed Furnace Service And Clean. Inspected Tubular Heat Exchanger Cells Finding No Failures At This Time. Inspected Blower Wheel, Evaporator Coil And Air Filter. Cleaned Flame Sensor, Spark Ignition Components, Burners And Crossovers (crossovers Were Completely Plugged Causing Improper Lighting). Cleared Inducer Signal Port. Cycled Furnace To Insure Proper Operation. Blower Motor And Inducer Motor Are Operating Properly Within Manufactures Specs. Furnace Is Heating Properly At This Time With A Temperature Rise Of 58°. Tested For Carbon Monoxide Finding 0ppm At This Time.
La Porte, IN
11-30-2021
Furnace Service And Repair La Porte, Indiana
Technician Invoice Notes: Call For No Heat And Thermostat Blank. Upon Arrival Found Thermostat Battery Terminals Corroded. Cleaned Terminals And Installed New Client Provided Batteries. Cleaned Flame Sensor As A Preventative Measure And Cycled Furnace To Ensure Proper Operation. Unit Is Heating Properly At This Time With A Temperature Rise Of Degrees.
La Porte, IN
11-08-2021
Furnace Service And Repair La Porte, Indiana
Technician Invoice Notes: Call To Re-light Pilot On Williamson Furnace. Re-lit Pilot And Observed Furnace Operation. Inspected Heat Exchanger Assembly And Found No Failures At This Time. Client Declined Any Further Diagnostic For The Air Conditioning System At This Time.
La Porte, IN
09-13-2021
Furnace Service And Repair La Porte, Indiana
Technician Invoice Notes: Call For No Heat. Upon Arrival Found Furnace Giving Code For Pressure Switch. Took Hose Off Of Pressure Switch To Find Water Gushing Out Of Inducer Housing. Furnace Cycled And Heated Properly After Removing Water. Checked Heat Exchanger Finding Wear But No Failures At This Time. Performed Carbon Monoxide Test Finding 0ppm At This Time. Gave Customer Options To Replace.
LA PORTE, IN
09-13-2021
Furnace Service And Repair La Porte, Indiana
Technician Invoice Notes: Upon Arrival Found Thermostat Displaying Low Battery. Replaced Batteries And Cycled Furnace To Insure Proper Operation. Furnace Is Heating Properly At This Time With A Temperature Rise Of 58°.
La Porte, IN
05-06-2021
Furnace Service And Repair La Porte, Indiana
Technician Invoice Notes: Upon Arrival Found 3” Furnace Venting Leaking At Multiple Glue Joints. Removed Small Section And Replaced With New 3” Sch 40 Pvc And Necessary Fittings. Tested Operation Of Repair By Cycling Furnace On And Off With No Issues At This Time.
La Porte, IN
04-28-2021