Water Or Steam Boiler Repair Laporte, Indiana
Technician Invoice Notes: Call For No Heat. Upon Arrival Found Boiler System Heating From Both First And Second Floor Zones. After Further Investigation Found First Floor Zone Valve Working Intermittently. Replaced First Floor Power Head And Cycled Boiler From Both Zones Several Times Observing Proper Operation. Boiler Satisfies At 180° With A Pressure Of Approximately 19 PSIG.
LaPorte, IN
02-01-2024
Water Or Steam Boiler Repair Laporte, Indiana
Technician Invoice Notes: Call For No Heat. Found Boiler Pump Bearing Assembly Locked Up At Arrival. Found Auto Vent Leaking On Boiler At Arrival. Replaced Pump Bearing Assembly And Reused Old Impeller Per Customers Request. Replaced Auto Vent On Boiler. Power Bled All Boiler Zones. Cycled Boiler System From Thermostat And Observed Unit Operation. All Radiation Is Heating Properly At This Time And The Boiler Cycles Off At 190° With A Pressure Of Approximately 20 PSIG.
LAPORTE, IN
04-20-2022
Water Or Steam Boiler Repair Laporte, Indiana
Technician Invoice Notes: Call To Install Client Provided Relief Valve. Installed Client Provided Boiler Relief Valve, Cycled Boiler And Observed Unit Operation. Boiler Is Heating Properly At This Time And Cycles Off At 160° With A Pressure Of Approximately 17 PSIG.
LaPorte, IN
01-28-2022
Water Or Steam Boiler Repair Laporte, Indiana
Technician Invoice Notes: Call For No Heat. Upon Arrival Found Pilot Assembly Orifice Plugged. Could Not Disassemble Rusted Pilot Assembly. Replaced Pilot Assembly And Cycled Boiler To Ensure Proper Operation. All Radiation Is Heating Properly At This Time And The Boiler Cycles Off At 180° With A Pressure Of Approximately 20 PSIG. Strongly Recommend Having Boiler System Serviced Annually For Preventative Maintenance Purposes.
LAPORTE, IN
11-30-2021
Water Or Steam Boiler Repair Laporte, Indiana
Technician Invoice Notes: Call For No Heat. Upon Arrival Found Pilot Assembly Orifice Plugged. Could Not Disassemble Rusted Pilot Assembly. Replaced Pilot Assembly And Cycled Boiler To Ensure Proper Operation. All Radiation Is Heating Properly At This Time And The Boiler Cycles Off At 180° With A Pressure Of Approximately 20 PSIG. Strongly Recommend Having Boiler System Serviced Annually For Preventative Maintenance Purposes.
LAPORTE, IN
11-18-2021
Water Or Steam Boiler Repair Laporte, Indiana
Technician Invoice Notes: Call For No Heat In Master Bedroom. Upon Arrival Found Master Bedroom Armstrong Furnace Failing To Ignite Due To Water Logged Inducer Draft Motor. After Further Investigation Found Plugged Condensate Drain. Cleared All Drain Lines And Cycled Furnace To Ensure Proper Operation. Unit Is Heating Properly At This Time With A Temperature Rise Of 54°. Also Ensured Proper Operation Of The Main Furnace Including Zone System. Main Furnace And Associated Zones Are Functioning Properly At This Time.
LaPorte, IN
11-15-2021
Water Or Steam Boiler Repair Laporte, Indiana
Technician Invoice Notes: Call For No Heat. Upon Arrival Found Boiler Receiving A Call For Heat From Two Zones And Vent Damper Motor In The Closed Position. After Further Investigation Found Vent Damper Sticking And Failed Control Relay Serving Circulator Pump. Set Damper Motor In The Normally Open Position And Replaced Control Relay. Cycled Boiler To Ensure Proper Operation And System Is Heating Properly At This Time. Boiler Cycles Off At 180° With A Pressure Of Approximately 17 PSIG.
LAPORTE, IN
11-08-2021
Water Or Steam Boiler Repair Laporte, Indiana
Technician Invoice Notes: Call For Boiler Relief Valve Leaking. Upon Arrival Found Relief Valve And Expansion Tank Failed. Installed New Expansion Tank, Client Supplied Relief Valve And New Bedroom Zone Valve Control. Also Installed A New Return Isolation Valve And New Boiler Drain For Future Maintenance And Air Purging. Serviced Boiler System, Cleaned Burners, Cleaned Pilot Assembly And Inspected Heat Exchanger. Cycled Boiler From Both Zones To Ensure Proper Operation And Unit Is Heating Properly At This Time And Cycles Off At 190° With A Pressure Of Approximately 20 PSIG. Recommend Having Boiler Serviced Annually For Preventative Maintenance Purposes.
LAPORTE, IN
06-28-2021
Water Or Steam Boiler Repair Laporte, Indiana
Technician Invoice Notes: Call For Galvanized Nipple Leaking From Well Tank Piping. Upon Arrival Found Nipple Leaking. Replaced Galvanized Nipple With Brass And Replaced Whole House Ball Valve And Adjacent Copper Piping. Cycled Well System To Ensure Proper Operation.
LaPorte, IN
06-28-2021
Water Or Steam Boiler Repair Laporte, Indiana
Technician Invoice Notes: Call For Boiler Making Noise And Auto Air Bleeder Spitting. Upon Arrival Found System Low On Pressure And Fill Valve Failed. Replaced Fill Reducing Valve And Expansion Tank. Set System To 12 PSIG Cold And Force Bled Radiation. Also Purged Individual Radiators And Cycled Boiler From Each Thermostat To Ensure Proper Operation Of All Zone Valve Controls. Boiler Is Heating Properly At This Time And Cycles Off At 180° With A Pressure Of Approximately 18 PSIG. Recommend Having Boiler Serviced Annually For Preventative Maintenance Purposes. Client Requests A Mailed Receipt.
LAPORTE, IN
03-12-2021
Water Or Steam Boiler Repair Laporte, Indiana
Technician Invoice Notes: Call For Boiler Operating Out Of Sequence. Upon Arrival Found Flame Signal Weak Causing Intermittent Ignition. Serviced Boiler System. Cleaned Burners, Cleaned Flame Sensor, Cleaned Spark Igniter, Inspected Heat Exchanger, Inspected Vent, Drained Expansion Tank, Tested Fill Reducing Valve, Tested Relief Valve And Cycled Boiler From Both Zones To Ensure Proper Operation. Observed Boiler Cycle Off At 180° With A Pressure Of Approximately 17 PSIG.
LAPORTE, IN
02-18-2021
Water Or Steam Boiler Repair Laporte, Indiana
Technician Invoice Notes: Call To Inspect Boiler System For Proper Operation Due To Louder Operation Than Normal. Upon Arrival Found Two Twinned Burnham High Efficiency Boilers In Operation. Master And Slave Boiler In High Fire Rate Has Amp Ratings Within The Allotted Range. Cycled Both Boilers Individually To Ensure Proper Operation. After Further Investigation Found Plugged Intake Piping Serving Master Boiler. Cleared Vent Obstruction And Both Units Are Functioning Properly At This Time. Explained To Client That Lower Thermostat Set Points In Cold Weather Will Allow The Boilers To Operate At Higher Fire Rates And May Seem Louder Than Usual.
LAPORTE, IN
02-15-2021
Water Or Steam Boiler Repair Laporte, Indiana
Technician Invoice Notes: Call For No Heat. Upon Arrival Found Boiler Cold And Circulator Pump Operating. After Further Investigation Found Loose Connection At Main Aquastat Control. Repaired Wiring And Cycled Boiler To Ensure Proper Operation. Ensured Aquastat Operation And Observed Boiler Cycle Off At 180°.
LAPORTE, IN
01-27-2021
Water Or Steam Boiler Repair Laporte, Indiana
Technician Invoice Notes: Replaced Boiler Circulator Pumps Per Proposal Details. Force Bled All Radiation And Cycled Boiler From All Zones To Ensure Proper Operation. All Radiation Is Heating Properly At This Time And The Boiler Cycles Off At Degrees With A Pressure Of Approximately 18 PSIG.
LaPorte, IN
01-20-2021
Water Or Steam Boiler Repair Laporte, Indiana
Remove Existing Relay Controls And Related Wiring As Needed.
Provide And Install New Relay Controls And Wiring As Needed To Operate The Existing Boiler And Existing Pumps With The Existing Thermostat Controls.
LAPORTE, IN
01-15-2021
Water Or Steam Boiler Repair Laporte, Indiana
Technician Invoice Notes: Drained Boiler System, Replaced Failed Reducing Valve And Added Isolation For Future Service As Part Of Proposal. Filled System To Approximately 12 PSIG Cold And Bled All Radiation. Cycled Boiler To Ensure Proper Operation And Unit Is Heating Properly At This Time. Boiler Cycles Off At 165° With A Pressure Of Approximately 19 PSIG.
LAPORTE, IN
12-31-2020